Transformer & Feeder Amps

kVA to Amps Calculator (Single & 3-Phase)

Substation transformer secondary breaker sizing, generator feeder cable selection. Calculates rated full-load current output for single-phase and 3-phase transformers, generators, and distribution switchgear.

kVA to Amps Calculator (Single & 3-Phase)
kVA
Volts
Phase
Calculated Result
--
Instant Calculation
Engineering Output
--
Auxiliary Output
--
Step-by-Step Derivation ▼ Show Steps
Governing Formula Verified Physics
1-Phase: I = (kVA × 1000) / V  |  3-Phase: I = (kVA × 1000) / (√3 × V)

Calculations adhere to standard electrical engineering physics and National Electrical Code (NFPA 70) regulations.

Engineering Principles & Calculations

This calculator uses the exact mathematical relationships between Apparent Power (kVA), Voltage (V), Phase Type (1-Phase / 3-Phase Line-to-Line) to determine Rated Current (Amperes / A). In practical installations, factors such as ambient raceway temperature, harmonic distortion, duty cycle continuous operation, and conductor impedance must be accounted for by a certified electrician.

Calculates rated full-load current output for single-phase and 3-phase transformers, generators, and distribution switchgear.

Typical Application & Industry Guidelines

Substation transformer secondary breaker sizing, generator feeder cable selection.

Reference Matrix

kVA to Amps Calculator (Single & 3-Phase) Benchmark Lookup Table

Standard 3-Phase kVAAmps @ 208VAmps @ 240VAmps @ 480V
15 kVA41.6 A36.1 A18.0 A
30 kVA83.3 A72.2 A36.1 A
45 kVA124.9 A108.3 A54.1 A
75 kVA208.2 A180.4 A90.2 A
112.5 kVA312.3 A270.6 A135.3 A
150 kVA416.4 A360.8 A180.4 A
300 kVA832.7 A721.7 A360.8 A
FAQ

Frequently Asked Questions

How many amps is a 75 kVA transformer at 480V 3-phase? +
Current = (75 × 1000) / (1.732 × 480) = 75,000 / 831.38 = 90.21 Amperes.
How many amps is a 75 kVA transformer at 208V 3-phase? +
Current = 75,000 / (1.732 × 208) = 75,000 / 360.27 = 208.18 Amperes.
What size secondary breaker is required for 75 kVA at 208V? +
At 208A full load current, applying standard 125% protection yields 208A × 1.25 = 260A, requiring a standard 250A or 300A main circuit breaker.